Function
The unit BI1 is equipped with an independent over (I>) and undercurrent supervision (I<) with seperate adjustable pickup values and trip delays. The measured current is continuously compared with the set reference values.
If the current exceeds or drops below the set value the relay trips after the time delay has elapsed.
Undercurrent supervision can be deactivated by turning potentiometer I</In to 0 %.

 

 

For more information please contact :

PT. SINAR ELEKTRINDO PERKASA

Phone : (+62) 21 580 6044-45

Whatsapp : (+62) 857 7950 9308

Email : sep_seg@yahoo.com

Technical data
Rated voltage Un :  24 V DC or 230 V AC ±20%
Power consumption :  3,3 W
Dropout to pickup ratio :  >97 %
Thermal load carrying capacity :  contionuously 4 x In
Returning time :  400 ms
Minimum operating time :  400 ms
Rated frequency :  50/60 Hz

 